HUMIDISTAT
WIRING INSTRUCTIONS
FGD-0027
v. 1.51
The humidistat can work with your Sensaphone to detect too high or too low a humidity level. The range
of the humidistat is 10% to 60%.
INSTRUCTIONS FOR 400, 800, 1400, 1800, 2800, EXPRESS II
When using the humidistat to detect too high a humidity level:
1. The normality of the sensor will be N.C.—“normally closed.”
2. Set the control knob to the ON position.
3. Connect the two wires from terminals #2 and #3 on the humidistat to any alert input.
4. Your Sensaphone may indicate that an alert condition exists. Press ALARM CANCEL to clear the
message.
5. Re-set the input configuration and/or the input type. Consult your owner’s manual for further
instructions.
6. Turn the humidistat control to the humidity setting you want to cause an alarm.
When using the humidistat to detect too low a humidity level:
1. The normality of the sensor will be N.O.— “normally open.”
2. Set the control knob to the OFF position.
3. Connect the two wires from terminals #2 and #3 on the humidistat to any alert input.
4. Your Sensaphone may indicate that an alert condition exists. Press ALARM CANCEL to clear the
message.
5. Re-set the input configuration and/or the input type. Consult your owner’s manual for further
instructions.
6. Turn the humidistat control to the humidity setting you want to cause an alarm.
INSTRUCTIONS FOR 2000, WEB600, SAT4D, CELL682 and SCADA 3000
When using the humidistat to detect too high a humidity level:
1. The normality of the sensor will be N.C.—“normally closed.”
2. Connect the two wires from terminals #2 and #3 on the humidistat to any input.
3. Program the input type as discussed in your owner’s manual.
4. Turn the humidistat control to the humidity setting you want to cause an alarm.
When using the humidistat to detect too low a humidity level:
1. The normality of the sensor will be N.O.—“normally open.”
2. Connect the two wires from terminals #2 and #3 on the humidistat to any input.
3. Program the input type as discussed in your owner’s manual.
4. Turn the humidistat control to the humidity setting you want to cause an alarm.
Note: See manufacturer’s insert for wall or duct mounting instructions.