Sensaphone
®
Express II User’s Manual
POWER [7]
Express II monitors AC power failure and low
battery condition. Power monitoring and low battery
monitoring is explained below.
1= AC Power
2= Battery
Power Failure
1. Power Failure Monitoring enable/disable—This
command enables or disables the power failure
detection. When enabled, Express II will monitor
power and dial out if a valid failure occurs. When
disabled, Express II will not dial out for a power
failure. 1 = disable, 2 = enable. The default is
enabled
.
2. Power Recognition Time—The power
recognition time is the length of time that a power
failure must exist continuously before Express II
will recognize it as an actual alarm and initiate
the dial out sequence. Power recognition time may
be programmed from 0 seconds to 12 hours. The
default is
5 minutes.
3. Alarm Reset Time—After power failure is
acknowledged, Express II stops the dial out
sequence. However, the power failure condition will
still exist until power is restored. If the power is not
restored after a certain amount of time, Express II
can be programmed to restart the dial out sequence.
This is called the alarm reset time. This parameter
may be programmed from 0 seconds to 12 hours.
If the alarm reset time is programmed to 0 seconds,
the feature is disabled. Express II will not restart
the dial out regardless of how long the alarm exists.
4. Dial Out Selection—You may program Express
II to call a specific set of Phone Contacts for power
failure only. This is called the Dialout Selection. To
return to the default setting, all contacts, press “9”
“9,and then press ENTER.
Sensaphone
®
Express II User’s Manual
POWER PARAMETERS
AC POWER
1) Press Program.
2) Press Power.
3) Power menu will appear. Press 1 for
AC Power Parameters.
The AC Power menu will then be
displayed.
1-Power Failure Monitoring:
1) At the AC Power menu press 1 for
Failure Monitor.
2) Press
1 to disable.
Press 2 to enable.
2-Power Recognition Time:
1) Press 2 at the AC Power menu.
2) Enter hours.
Enter minutes.
Enter seconds.
3-Alarm Reset Time:
1) Return to the AC Power menu. Press 3
for Alarm Reset time.
2) Enter hours.
Enter minutes.
Enter seconds.
4-Dialout Selection:
1) Press 4 at the AC Power menu for Dial
Out Selection.
2) Enter the list of position numbers,
(1-
48), for those contacts to be dialed by
Express II in the event of AC Power
Failure. (Failure monitor must be
enabled
.)